Description
Victron MultiPlus II 5000/48/70-50 Inverter/Charger is an Inverter/Charger with device networking built-in, the MultiPlus-II GX communicates with a solar charger, batteries, and other devices to control a grid-connected, off-grid, or remote power installation. Capable of parallel operation for increased power output or battery charge rates, the MultiPlus-II GX can also be configured for a three-phase supply. A host of advanced features – such as uninterrupted power supply, setting load limits, and supplementing limited grid-power availability with battery power – can all be controlled straight from your phone or smart device. Remote monitoring is also possible.
The MultiPlus-II combines the functions of the MultiPlus and the MultiGrid. It has all the features of the MultiPlus, plus an external current transformer option to implement PowerControl and PowerAssist and to optimise self-consumption with external current sensing (max. 32A).
PowerAssist:Â The MultiPlus-II will prevent overload of a limited AC source, such as a generator or shore power connection. First, battery charging will automatically be reduced when otherwise an overload occurs. The second level will boost the output of a generator or shoreside supply with power from the battery.
The MultiPlus-II is the key component in a Victron ESS system, providing the flexibility to combine with MPPT Solar Chargers or Grid-tie PV Inverters.
UPS function:Â In the event of a grid failure or when shore or generator power is disconnected, the inverter within the Multi is automatically activated and takes over the supply to the connected loads. This happens so fast (less than 20 milliseconds) that computers and other electronic equipment will operate without disruption.
Monitor and control your system locally (LAN) or remotely via the internet from anywhere in the world using the free VRM app. Access can be from a phone, tablet, laptop or PC for multiple operating systems. There is no end to the level of control via the required Color Control GX or Venus GX, from adjusting your Multi to auto-starting a back generator and more… This Multiplus comes integrated with GX.
A MultiPlus, plus ESS (Energy Storage System) functionalityÂ
The MultiPlus-II is a multifunctional inverter/charger with all the features of the MultiPlus, plus an external current sensor option which extends the PowerControl and PowerAssist function to 50 A resp. 100 A.Â
The MultiPlus-II is ideally suited for professional marine, yachting, vehicle and land based off -grid applications.Â
https://ve3.nl/6H
Connection Area MultiPlus-II 3k
It also has built-in anti-islanding functionality, and an increasingly long list of country approvals for ESS application. Several system configurations are possible. For more detailed information see the ESS Design and configuration manual. PowerControl and PowerAssist – Boosting the capacity of the grid or a generatorÂ
A maximum grid or generator current can be set. The MultiPlus -II will then take account of other AC loads and use whatever is extra for battery charging, thus preventing the generator or grid from being overloaded (PowerControl function).Â
PowerAssist takes the principle of PowerControl to a further dimension. Where peak power is so often required only for a limited period, the MultiPlus-II will compensate insufficient generator, shore or grid power with power from the battery. When the load reduces, the spare power is used to recharge the battery.Â
Solar energy: AC power available even during a grid failureÂ
The MultiPlus-II can be used in off grid as well as grid connected PV and other alternative energy systems. It is compatible with both solar charge controllers and grid -tie inverters.Â
Two AC OutputsÂ
The main output has no break functionality. The MultiPlus -II takes over the supply to the connected loads in the event of a grid failure or when shore/generator power is disconnected. This happens so fast (less than 20 milliseconds) that computers and othe r electronic equipment will continue to operate without disruption.Â
The second output is live only when AC is available on the input of the MultiPlus -II. Loads that should not discharge the battery, like a water heater for example, can be connected to this output.Â
Virtually unlimited power thanks to parallel and three phase operationÂ
Up to 6 Multis can operate in parallel to achieve higher power output. Six 48/5000/70 units, for example, will provide 25 kW / 30 kVA output power with 420 Amps charging capacity.Â
In addition to parallel connection, three units of the same model can be configured for three phase output. But that’s not all: up to 6 sets of three units can be parallel connected for a 75 kW / 90 kVA inverter and more than 1200 Amps charging capacity.Â
The MultiPlus-II 8k, 10k, and 15k models can only be connected in parallel if an external AC transfer switch is used. For more information see the MultiPlus-II External Transfer Switch application manual .Â
On-site system configuring, monitoring and controlÂ
Settings can be changed in a matter of minutes with VEConfigure software (computer or laptop and MK3 -USB interface needed).Â
Several monitoring and control options are available: Cerbo GX, Ekrano GX, laptop, computer, Bluetooth (with the optional VE.Bus Smart dongle), Battery Monitor, Digital Multi Control Panel.Â
Remote configuring and monitoringÂ
Install a Cerbo GX or other GX product to connect to the internet.Â
Operational data can be stored and displayed on our VRM (Victron Remote Management) website, free of charge. When connected to the internet, systems can be accessed remotely, and settings can be changed.Â
Standard marine, mobile or off -grid applicationÂ
Loads that should shut down when AC input power is not available can be connected to a second output (not shown). These loads will be taken into account by the PowerControl and PowerAss ist function in order to limit AC input current to a safe value when AC power is available.Â
Grid parallel topology with MPPT solar charge controller The MultiPlus-II will use data from the external AC current sensor (must be ordered separately) or power meter to optimis e self consumption a nd, if required, to prevent grid feed. In case of a power outage, the MultiPlus-II will continue to supply the critical loadsÂ
Ekrano GX or Cerbo GXÂ Â
Provides intuitive system control and monitoring and enables access to our free remote monitoring website: the VRM Online Portal.Â
VRM PortalÂ
Our free remote monitoring website (VRM) will display all system data in a comprehensive graphical format. System settings can be changed remotely via the portal. Alarms can be received by e -mail or push notification.Â
VRM app helps you monitor and manage  your Victron Energy  system from your smart  phone and tablet.  Available for both iOS  and Android.Â
TECHNICAL DATASHEET
| MultiPlus-II 230V | 12/3000/120-3224/3000/70-32 48/3000/35-32 | 12/5000/220-5024/5000/120-50 48/5000/70-50 | 48/8000/Â
110-100 |
48/10000/Â
140-100 |
48/15000/Â
200-100 |
| PowerControl & PowerAssist | Yes | ||||
| Transfer switch | 32 A | 50 A | 100 A | 100 A | 100 A |
| Maximum AC input current | 32 A | 50 A | 100 A | 100 A | 100 A |
| INVERTER | |||||
| DC Input voltage range | 12 V – 9,5–17 V 24 V – 19–33 V 48 V – 38-66 V | ||||
| Output | Output voltage: 230 VAC ± 2 % Frequency : 50 Hz ± 0,1 % (1) | ||||
| Cont. output power at 25 °C (3) | 3000 VA | 5000 VA | 8000 VA | 10000 VA | 15000 VA |
| Cont. output power at 25 °C | 2400 W | 4000 W | 6400 W | 8000 W | 12000 W |
| Cont. output power at 40 °C | 2200 W | 3700 W | 5500 W | 7000 W | 10000 W |
| Cont. output power at 65 °C | 1700 W | 3000 W | 4000 W | 6000 W | 7000 W |
| Max apparent feed-in power | 3000 VAÂ | 5000 VAÂ | 8000 VAÂ | 10000 VAÂ | 15000 VA |
| Peak power | 5500 W | 9000 W | 15000 W | 18000 W | 27000 W |
| Maximum efficiency | 93%/94%/95% | 95%96%/96% | 95% | 96% | 95% |
| Zero load power | 13 / 13 / 11 W | 15/18/18 W | 29 W | 38 W | 55 W |
| Zero load power in AES mode | 9 / 9 / 7 W | 11/12/12 W | 19 W | 27 W | 39 W |
| Zero load power in Search mode | 3 / 3 / 2 W | 3 / 3 / 2 W | 3 W | 4 W | 6 W |
| CHARGER | |||||
| AC Input | Input voltage range: 187 -265 VAC
Input frequency: 45 – 65 Hz |
||||
| Charge voltage ‘absorption’Â | 14,4 / 28,8 / 57,6 V | ||||
| Charge voltage ‘float’Â | 13,8 / 27,6 / 55,2 V | ||||
| Storage mode | 13,2 / 26,4 / 52,8 V | ||||
| Max. battery charge current (4)Â | 120 /70 / 35 AÂ | 220/120/ 70 A | 110 AÂ | 140 AÂ | 200 A |
| Battery temperature sensor | Yes | ||||
| GENERAL | |||||
| Auxiliary output | Yes (32 A) | Yes (50 A) | |||
| External AC current sensor (optional)Â | 50 A or 100 A | ||||
| Programmable relay ( 5)Â | Yes | ||||
| Protection (2) | a – g | ||||
| VE.Bus communication port | For parallel and three phase operation,
remote monitoring and system integration |
||||
| General purpose com. port | Yes, 2x | ||||
| Remote on-off | Yes | ||||
| Operating temperature range | -40 to +65 °C (fan assisted cooling) | ||||
| Humidity (non -condensing) | max 95 % | ||||
| Maximum altitude | 2000 m. | ||||
| ENCLOSURE | |||||
| Material & Colour | Steel, blue RAL 5012 | ||||
| Protection category | IP22 | ||||
| Battery-connection | M8 bolts | Four M8 boltsÂ
(2 plus and 2 minus connections) |
|||
| 230 VAC-connection | Screw terminals 13 mm ² (6 AWG) | Bolts M6 | Bolts M6 | Bolts M6 | |
| Weight kg | 19 kg | 33/ 30/ 30 kg | 42 kg | 49 kg | 80 kg |
| Dimensions (hxwxd) mm | 546 x 275 x 147499 x 268 x 141 499 x 268 x 141 | 702 x 345 x 152 607 x 330 x 149 565 x 320 x 149 | 642 x 363 x 206Â | 677 x 363 x 206Â | 810 x 405 x 217 |
| STANDARDS | |||||
| Safety | EN-IEC 60335-1, EN-IEC 60335-2-29,
EN-IEC 62109-1, EN-IEC 62109-2 |
||||
| Emission, Immunity | EN 55014-1, EN 55014-2
EN-IEC 61000-3-2, EN-IEC 61000-3-3Â IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3 |
||||
| Uninterruptible power supply | Please consult the certificates on our website. | ||||
| Anti-islanding | Please consult t he certificates on our website. | ||||
Protection key: Â
- Output short circuit
- Â overload
- battery voltage too high
- Â battery voltage too lowÂ
- Â temperature too high
- Â 230 VAC on inverter output
- Â input voltage ripple too highÂ
VE.Bus Smart Dongle For monitoring and  control via Bluetooth together with the  VictronConnect app.Â
Interface MK3 -USBÂ Â
Needed to configure the MultiPlus, Can be used with the VictronConnect app or Â
VictronConnect appÂ
Current sensor 100A:50mA To implement PowerControl and PowerAssist and to optimize self-consumption with external current sensing. Â
Victron MultiPlus II 5000/48/70-50 Inverter/Charger datasheet